Level 2 40A/48A/60A home & commercial charging. We do load calculations (not guesswork), run dedicated copper circuits, install hardwired or NEMA 14-50, handle permits, and set up load management so your panel doesn’t overload. HQ Everett, dispatched in all 50 states.

Two contractors quoted 40A breaker on 8AWG for 48A charger (fire hazard). We caught it. We follow NEC 625.41: continuous load = 125% breaker & wire.
Sometimes. If load calc >80% of service, we recommend 200A upgrade or load management system. We give both options with pricing.
40A circuit (32A charging): ~25 mi/hr. 60A circuit (48A charging): ~37 mi/hr. Depends on car. We size for your daily miles, not max spec.
Yes — we do multi-unit, workplace, fleet depots nationwide. Load sharing, 277/480V, pedestal mounts, networked billing.